CCR Warning – Comms 24V Missing
URL Name
CCR-Warning-Comms-24V-Missing
Summary
Describes the Comms 24V Missing condition on the Type L-828 / L-829 CCR and outlines the manual-listed attempt to correct procedure.

Content

Warning Description

The CCR was set up to monitor a 24VDC backup power supply. This warning occurs when the monitor is enabled and the 24VDC backup is missing. If no 24VDC backup power supply is installed, this warning will only be seen if the monitor is enabled in the Configuration Menu.

Attempt to correct

  • Verify the backup power supply is operational using a DMM.
  • If no backup supply is connected: the option for monitoring was unintentionally enabled. To disable, navigate to: Configuration Menu > Monitor Config > Comms 24V Monitor > [Disable]

Airport Lighting Company | Type L-828 / L-829 Ferroresonant Constant Current Regulator

Constant Current Regulator

Related Articles

  • CCR Warning – Local Comms Mode
    Number of Views39
  • CCR Warning – Comm Loss - Failsafe
    Number of Views34
  • CCR Warning – No Comms Ch A
    Number of Views47
  • CCR Warning – No Comms Ch B
    Number of Views37
  • CCR Warning – High Temperature
    Number of Views48

Trending Articles

  • L861 LED Medium Intensity Elevated Edge Light - Replacement Parts
  • L-828, Type L-829 Ferroresonant Constant Current Regulator (CCR) - Completing In-Field Recalibrations
  • L-828, Type L-829 Ferroresonant Constant Current Regulator (CCR) - Product Overview
  • Performing Megger Testing for Airfield Lighting Systems
  • L-828, Type L-829 Ferroresonant Constant Current Regulator (CCR) - Fuse Overview (F1 through F5 Functions)
Powered by Salesforce Logo
Loading
CCR Warning – Comms 24V Missing