L-849-V-A/E / L-849-I-A/E Unidirectional Runway Approach Lights - Set Up Procedure for a 3 Step CCR
URL Name
L-849-V-A-E-L-849-I-A-E-Unidirectional-Runway-Approach-Lights---Set-Up-Procedure-for-a-3-Step-CCR
Summary
The switching levels will likely need “fine tune” adjustments in the field due to the many variables that can affect these adjustments. This article describes the setup adjustment procedure for a 3 step CCR

Content

Overview

It is likely that the switching levels will have to be fine tuned upon installation due to specific conditions at your site such as the type of CCR in use and other loads that may be driven by the same CCR. Adjustments are made at the CSM-112 Current Sensing Module in the Master Unit

Procedure

1. Set the CCR to Step 1 (4.8 amps).

2. Open the cover of the master unit, and set the interlock switch to the ‘service’ position (pull up on the stem of the switch). The unit may or may not begin to flash depending the existing PCB-101 potentiometer adjustments.

3. At PCB-101, (See Figure 7) adjust all three potentiometers, LOW; MED; & HIGH, fully counter clockwise (CCW).

  • If the unit had been flashing it should now stop flashing, but PCB-1 (the main circuit board) should still be active.

4. Carefully re-adjust the LOW potentiometer CW until its adjacent LED comes on. Flashing should begin at Low intensity.

  • If the unit fails to flash it may be necessary to proceed to the Troubleshooting section of this manual on Page 17.

5. Set the CCR to Step 2 (5.5 amps).

  • Carefully adjust the MED potentiometer CW until its adjacent LED comes on. The unit should now flash at Medium intensity.

6. Set the CCR to Step 3 (6.6 amps).

  • Carefully adjust the HIGH potentiometer CW until its adjacent LED comes on. The unit should now flash at High intensity.

7. Set the CCR back to Step 2.

  • The HIGH LED should turn off. If it does not, adjust the HIGH potentiometer
    incrementally CCW until it does. The unit should then flash at Medium intensity.

8. Set the CCR to Step 1.

  • The MED LED should turn off. If it does not, adjust the MED potentiometer incrementally CCW until it does. The unit should then flash at Low intensity.

9. It is advisable to run through the CCR steps once more to verify that switching is correct. Make any necessary adjustments to the potentiometers to achieve correct switching by repeating the steps above.

10. No adjustments are required at a slave unit.


L-849-V-A/E / L-849-I-A/E Unidirectional Runway Approach Lights

Runway End Identifier Light

Related Articles

  • L-849-V-A/E / L-849-I-A/E Unidirectional Runway Approach Lights - Set Up Procedure for a 5 Step CCR
    Number of Views28
  • L-849-V-A/E / L-849-I-A/E Unidirectional Runway Approach Lights - Set Up Procedure for Single Intensity
    Number of Views41
  • L-849-V-A/E / L-849-I-A/E Unidirectional Runway Approach Lights - Available Options
    Number of Views40
  • L-849-V-A/E / L-849-I-A/E Unidirectional Runway Approach Lights - Installation Instructions
    Number of Views62
  • L-849-V-A/E / L-849-I-A/E Unidirectional Runway Approach Lights - System Operation
    Number of Views36

Trending Articles

  • L-862(L), L-862E(L) High Intensity LED Runway Light - Replacement Parts
  • How a Ferroresonant Constant Current Regulator Works
  • L-880(L), L-881(L) Precision Approach Path Indicator Lights (PAPI) - Installation Instructions
  • L-880(L), L-881(L) Precision Approach Path Indicator Lights (PAPI) - Performance Information
  • CCR Warning – Mismatch - Failsafe
Powered by Salesforce Logo
Loading
L-849-V-A/E / L-849-I-A/E Unidirectional Runway Approach Lights - Set Up Procedure for a 3 Step CCR