CCR Fault – Open Circuit
URL Name
CCR-Fault-Open-Circuit
Summary
Explains the Open Circuit fault condition on the Type L-828 / L-829 CCR, when it occurs, and the manual-listed attempt to correct procedure.

Content

Fault Description

The CCR has determined that it is trying to drive current into an open circuit. This fault will occur when the output voltage increases but the output current does not scale to the selected setting. This fault will generally occur only if there is a problem with the airfield circuit or at a new installation.

Attempt to Correct

If this error occurs during CCR installation:

 Refer to: Adjust the Open Circuit Duration

If this error occurs during normal operation it must be determined if the issue is with the CCR or airfield circuit.

  • Put the CCR in Local mode, and then disconnect CCR supply power.
  • Within the CCR, install a wire jumper, or pull an S-1 Cutout handle, like described in Terminating CCR Connections.
  • Re-energize the CCR, and turn it on to the first brightness step.
  • If the CCR continues to present the fault, contact Airport Lighting Company. Otherwise, consult an electrician to diagnose problems with the airfield circuit.

 

Airport Lighting Company | Type L-828, Type L-829 Ferroresonant Constant Current Regulator

Constant Current Regulator

Related Articles

  • L-828, Type L-829 Ferroresonant Constant Current Regulator - Adjust Open Circuit Threshold Duration
    Number of Views107
  • CCR Fault – Door Open Trip
    Number of Views69
  • CCR Fault – Over Voltage
    Number of Views51
  • CCR Fault – Over Current
    Number of Views49
  • CCR Fault – Unknown Fault
    Number of Views41

Trending Articles

  • Performing Megger Testing for Airfield Lighting Systems
  • L-828, Type L-829 Ferroresonant Constant Current Regulator (CCR) - Operating Modes and Output Current Settings
  • L-862(L), L-862E(L) High Intensity LED Runway Light - Installation Instructions
  • L-849(L) REIL Runway End Identification Light/L-859(L) ODAL OMNI Directional Approach Light - Installation Instructions
  • Troubleshooting an L849(L) SAL-1030 Runway End Identifier Light (REIL) System
Powered by Salesforce Logo
Loading
CCR Fault – Open Circuit