CCR Fault – Over Current
URL Name
CCR-Fault-Over-Current
Summary
Explains the Over Current fault condition on the Type L-828 / L-829 CCR and the manual-listed attempt to correct procedure.

Content

Fault Description

Per FAA specifications, this fault will occur in one of two conditions.

The output current must meet one of the following:

  • Be 5% over nominal current output for 5 seconds.
  • Be 25% over nominal current output for 1 second.

This fault may be caused by hardware failures.

Attempt to Correct

  • Put the CCR into Local mode and turn output off.
  • Open the CCR door and do a visual inspection for signs of damage.
  • Pull the door switch plunger laterally toward you to bypass the door interlock.
  • Turn the CCR on to the first brightness step.
  • Check to see if the solid state relay (SSR) coil indicator is lit up.
  • Contact Airport Lighting Company.

Airport Lighting Company | Type L-828, Type L-829 Ferroresonant Constant Current Regulator

Constant Current Regulator

Related Articles

  • CCR Fault – Over Voltage
    Number of Views64
  • CCR Fault – No Current
    Number of Views66
  • CCR Fault – Current Asymmetry
    Number of Views78
  • CCR Fault – Unknown Fault
    Number of Views49
  • CCR Fault – Door Open Trip
    Number of Views72

Trending Articles

  • L-862(L), L-862E(L) High Intensity LED Runway Light - Installation Instructions
  • L-880(L)/L-881(L) Precision Approach Path Indicator (PAPI) - Overview and Application
  • Troubleshooting an L849(L) SAL-1030 Runway End Identifier Light (REIL) System
  • Testing a Bridge Rectifier
  • L-858 I-LUX/D-Lux Guidance Sign - Light Engine Replacement
Powered by Salesforce Logo
Loading
CCR Fault – Over Current