Control Transformer – 15VAC and 120VAC Outputs in the CCR
URL Name
Control-Transformer-15VAC-and-120VAC-Outputs-in-the-CCR
Summary
Explains the function of the control transformer and its role in supplying low-voltage control power within the Type L-828 and L-829 Constant Current Regulators.

Content

Overview


The control transformer provides low-voltage power for the CCR control circuitry. It steps down the incoming line voltage to supply power for control circuits, DCMU, firing card, input contactor coil, and remote control circuitry. The control transformer is separate from the main ferroresonant transformer used for output regulation.

Output Voltages


The control transformer provides 15 VAC for internal control functions and 120 VAC for certain control and remote interface functions. These voltages power the regulation and monitoring electronics.

Function Within the System


The control transformer supplies operating power to the DCMU, energizes the input contactor coil, provides reference voltage for control logic, and supports remote control input circuits. Without proper control transformer output, the CCR will not operate correctly.

Startup Behavior


When input power is applied, the control transformer energizes. Control circuits power up. The DCMU display becomes active. The system becomes ready to receive ON/OFF commands. If control voltage is absent, the display may not power up, the input contactor may not energize, and the CCR may appear inoperative.

Isolation and Safety


The control transformer provides electrical isolation between line voltage input and low-voltage control circuitry. Even though control voltages are lower than output circuit voltage, they must still be treated as energized circuits until verified safe.

Airport Lighting Company | Type L-828, Type L-829 Ferroresonant Constant Current Regulator

Constant Current Regulator

Related Articles

  • Ferroresonant Transformer – Function and Role in the CCR
    Number of Views42
  • Verifying Isolation Transformer Output Current / Fixture Input Current
    Number of Views156
  • Firing Card – Control Interface and Function in the CCR
    Number of Views51
  • L-828, Type L-829 Ferroresonant Constant Current Regulator (CCR) - Operating Modes and Output Current Settings
    Number of Views94
  • Current Transformers (CTs) – Function in the CCR
    Number of Views41

Trending Articles

  • Performing Megger Testing for Airfield Lighting Systems
  • L-828, Type L-829 Ferroresonant Constant Current Regulator (CCR) - 24V Externally Powered Remote Wiring
  • Troubleshooting an L-880(L), L-881(L) Precision Approach Path Indicator Lights (PAPI)
  • L-828, Type L-829 Ferroresonant Constant Current Regulator (CCR) - Understanding the S-1 Cutout
  • L-849-V-A/E / L-849-I-A/E Unidirectional Runway Approach Lights - Set Up Procedure for a 3 Step CCR
Powered by Salesforce Logo
Loading
Control Transformer – 15VAC and 120VAC Outputs in the CCR