L-828, Type L-829 Ferroresonant Constant Current Regulator (CCR) - Maintenance
URL Name
L-828-Type-L-829-Ferroresonant-Constant-Current-Regulator-CCR---Maintenance
Summary
This article lists the recommended regular maintenance actions for the L-828, Type L-829 Ferroresonant Constant Current Regulator to ensure continued trouble-free operation

Content

Maintenance Guideline

Preventative Maintenance schedules and procedures for Constant Current Regulators are outlined in FAA Advisory Circular 150/5340-26, Section 5.2. Airport Lighting Company recommends the following lists are used to accompany the procedures detailed in AC 150/5340-26.

Monthly CCR PM Task List

  • Complete an exterior visual inspection of the CCR. Look for blockage of the vents on the front door, the top of the enclosure, and the back of the enclosure.
  • General housekeeping; wipe down the CCR as needed to prevent dust buildup.
  • In Local mode: cycle through the brightness steps and complete a visual inspection of circuit fixtures to ensure correct operation.
  • With CCR power disconnected: complete an interior visual inspection. Look for blockages of the vents on the front door, as well as the top and rear of the enclosure.
  • If large amounts of dust are present, consider using electronics compressed-gas duster to blow out dust from CCR components. Vacuum / wipe up any dust.
  • Complete a visual inspection of airfield circuit terminations and supply feed lines. Look for loose wires, terminal or wire degradation, etc.

Yearly CCR PM Task List 

  • Complete an exterior visual inspection of the CCR. Look for blockage of the vents on the front door, the top of the enclosure, and the back of the enclosure.
  • General housekeeping; wipe down the CCR as needed to prevent dust buildup. 
  • In Local mode: cycle through the brightness steps and complete a visual inspection of circuit fixtures to ensure correct operation.
  • Verify the correct calibration of the CCR. Refer to How to Determine if Recalibration is Needed for more information.
  • Verify the calibration of the IRMS / Megger, if equipped. To recalibrate, refer to IRMS / Megger Calibration.
  • With CCR power disconnected: complete an interior visual inspection. Look for blockages of the vents on the front door, as well as the top and rear of the enclosure.
  • Use electronics compressed-gas duster to blow out dust from CCR components. Vacuum / wipe up any dust.
  • Complete a thorough inspection of airfield terminations and supply feed lines. Look for loose wires, terminal or wire degradation, etc. Verify that all connections pass a “tug test”, output connection bolts are tight, and connection lugs are tight.

 

Airport Lighting Company | Type L-828, Type L-829 Ferroresonant Constant Current Regulator

Constant Current Regulator

Related Articles

  • L-828, Type L-829 Ferroresonant Constant Current Regulator (CCR) - Product Overview
    Number of Views134
  • L-828, Type L-829 Ferroresonant Constant Current Regulator (CCR) - Fuse Overview (F1 through F5 Functions)
    Number of Views142
  • L-828, Type L-829 Ferroresonant Constant Current Regulator (CCR) - Operating Modes and Output Current Settings
    Number of Views95
  • L-828, Type L-829 Ferroresonant Constant Current Regulator (CCR) - Understanding the CCR Display Screen
    Number of Views74
  • How a Ferroresonant Constant Current Regulator Works
    Number of Views81

Trending Articles

  • Performing Megger Testing for Airfield Lighting Systems
  • Troubleshooting an L-880(L), L-881(L) Precision Approach Path Indicator Lights (PAPI)
  • L-880(L), L-881(L) Precision Approach Path Indicator Lights (PAPI) - Leveling and Tilting the Light Head (Setting the glid…
  • Testing a Bridge Rectifier
  • L-849-V-A/E / L-849-I-A/E Unidirectional Runway Approach Lights - Set Up Procedure for a 3 Step CCR
Powered by Salesforce Logo
Loading
L-828, Type L-829 Ferroresonant Constant Current Regulator (CCR) - Maintenance