Output Surge Arrestors – Function in the CCR
URL Name
Output-Surge-Arrestors-Function-in-the-CCR
Summary
Explains the purpose of the output surge arrestors and their role in protecting the Type L-828 and L-829 Constant Current Regulators from transient conditions on the series circuit.

Content

Overview


Output surge arrestors are installed on the CCR output side. Their purpose is to protect the regulator and associated components from transient voltage conditions originating on the series lighting circuit.

Primary Function


The output surge arrestors limit transient overvoltage conditions. They protect internal transformer and control components. They help reduce damage caused by lightning or switching events on the field circuit. The series circuit can experience transient events due to lightning strikes near airfield circuits, cable faults, switching operations, or ground disturbances. The arrestors provide a path to divert excessive voltage.

Location in the System


Output surge arrestors are connected on the regulator’s output terminals. They operate independently of the DCMU and control system. Their function is protective, not regulatory.

Protection Scope


The output surge arrestors protect the ferroresonant transformer windings, SSR circuitry, firing card, current transformers, and other internal components exposed to output voltage. They do not regulate output current during normal operation. They only respond during transient conditions.

Interaction with Open-Circuit Conditions


The surge arrestors do not eliminate open-circuit voltage rise. They are intended to clamp transient spikes, not steady-state voltage conditions. Open-circuit hazards remain present even when surge arrestors are installed.

Service and Safety


Before servicing output components, de-energize input power. Follow proper lockout/tagout procedures. Verify absence of voltage. Output terminals may carry hazardous voltage. Surge arrestors are connected to the output circuit and must be treated as energized until verified safe.

Airport Lighting Company | Type L-828, Type L-829 Ferroresonant Constant Current Regulator

Constant Current Regulator

Related Articles

  • Input Surge Arrestor – Function in the CCR
    Number of Views49
  • Firing Card – Control Interface and Function in the CCR
    Number of Views51
  • Solid State Relay (SSR) – Function in the CCR
    Number of Views43
  • Current Transformers (CTs) – Function in the CCR
    Number of Views41
  • L-828, Type L-829 Ferroresonant Constant Current Regulator (CCR) - CCR Keypad Button Functions
    Number of Views246

Trending Articles

  • Performing Megger Testing for Airfield Lighting Systems
  • L-828, Type L-829 Ferroresonant Constant Current Regulator (CCR) - 24V Externally Powered Remote Wiring
  • Troubleshooting an L-880(L), L-881(L) Precision Approach Path Indicator Lights (PAPI)
  • L-828, Type L-829 Ferroresonant Constant Current Regulator (CCR) - Understanding the S-1 Cutout
  • L-849-V-A/E / L-849-I-A/E Unidirectional Runway Approach Lights - Set Up Procedure for a 3 Step CCR
Powered by Salesforce Logo
Loading
Output Surge Arrestors – Function in the CCR