L-828, Type L-829 Ferroresonant Constant Current Regulator (CCR) - Adjusting IRMS Warning and Alarm Thresholds
URL Name
Adjusting-IRMS-Warning-and-Alarm-Thresholds
Summary
Explains how to configure and adjust insulation resistance warning and alarm thresholds in a CCR equipped with IRMS functionality.

Content

Overview

The IRMS system allows configurable resistance thresholds that determine when a warning or alarm is generated. Proper threshold configuration ensures early detection of insulation degradation, avoidance of nuisance alarms, and reliable system monitoring. Threshold values must reflect installation conditions and maintenance policy.

Understanding Threshold Levels

Two primary levels are available: Warning Threshold generates a warning when insulation resistance drops below this value and does not necessarily disable CCR operation. Alarm Threshold generates a fault condition when resistance drops below this value and may disable output depending on configuration. The alarm threshold is typically set lower than the warning threshold.

When to Adjust Thresholds

Adjustment may be necessary when commissioning a new installation, establishing a baseline resistance value, environmental conditions influence readings, nuisance warnings occur, or maintenance standards change. Do not arbitrarily increase thresholds to suppress valid warnings.

Configuration Procedure

Power the CCR. Press CONFIG. Enter password 9999. Navigate to IRMS or Megger settings. Locate Warning Threshold setting. Enter desired resistance value. Locate Alarm Threshold setting. Enter desired resistance value. Save configuration and exit menu.

Setting Appropriate Values

Thresholds should be based on historical baseline insulation resistance, manufacturer or site maintenance standards, and environmental conditions. If baseline resistance is known, set warning threshold above alarm threshold. Ensure alarm threshold reflects unacceptable insulation condition. Trending historical values improves accuracy.

After Adjusting Thresholds

After updating values, verify settings are saved. Monitor IRMS readings. Confirm warnings and alarms trigger appropriately. Document new threshold settings for maintenance records.

Troubleshooting Threshold Issues

If alarms occur unexpectedly, compare current resistance reading to historical values. Inspect field circuit for moisture or damage. Verify threshold settings are appropriate. If alarms never occur despite known issues, confirm thresholds are not set too low. Verify IRMS is enabled.

Safety Reminder

Adjusting IRMS thresholds does not correct insulation faults. Investigate and correct the root cause of low insulation resistance before returning the CCR to service.


Airport Lighting Company | Type L-828, Type L-829 Ferroresonant Constant Current Regulator

Constant Current Regulator

Related Articles

  • L-828, Type L-829 Ferroresonant Constant Current Regulator (CCR) - Product Overview
    Number of Views134
  • L-828, Type L-829 Ferroresonant Constant Current Regulator (CCR) - Maintenance
    Number of Views62
  • L-828, Type L-829 Ferroresonant Constant Current Regulator (CCR) - Configuring Automatic Megger (IRMS)
    Number of Views47
  • L-828, Type L-829 Ferroresonant Constant Current Regulator (CCR) - Fuse Overview (F1 through F5 Functions)
    Number of Views140
  • L-828, Type L-829 Ferroresonant Constant Current Regulator (CCR) - Operating Modes and Output Current Settings
    Number of Views93

Trending Articles

  • Performing Megger Testing for Airfield Lighting Systems
  • Troubleshooting an L-880(L), L-881(L) Precision Approach Path Indicator Lights (PAPI)
  • L-880(L)/L-881(L) Precision Approach Path Indicator (PAPI) - Overview and Application
  • L-828, Type L-829 Ferroresonant Constant Current Regulator (CCR) - Understanding the S-1 Cutout
  • L-828, Type L-829 Ferroresonant Constant Current Regulator (CCR) - 24V Externally Powered Remote Wiring
Powered by Salesforce Logo
Loading
L-828, Type L-829 Ferroresonant Constant Current Regulator (CCR) - Adjusting IRMS Warning and Alarm Thresholds