L-828, Type L-829 Ferroresonant Constant Current Regulator (CCR) - CCR Keypad Button Functions
URL Name
CCR-Keypad-Button-Functions
Summary
Explains the function of each front-panel keypad button on the CCR Digital Control and Monitoring Unit (DCMU).

Content

Overview

The CCR front panel keypad allows operators to control and monitor the regulator. Keypad buttons provide access to operational control, mode selection, fault and warning review, and configuration settings. Understanding each button prevents improper operation.

ON Button

Pressing ON commands the CCR to energize. When pressed, the input contactor is commanded to close. Output current begins regulating at the selected brightness step. If the CCR does not turn ON, verify no active fault is present. Confirm proper control voltage. Verify S-1 cutout position.

OFF Button

Pressing OFF commands the CCR to shut down. When pressed, the input contactor opens. Output current is disabled. OFF overrides active step selection.

LOCAL Button

Pressing the arrow keys marked LOCAL places the CCR under front-panel control. In Local mode, brightness steps are selected from the keypad. Remote wiring and network commands are ignored. Use Local mode during commissioning, troubleshooting or regular usage without a remote.

REMOTE Button

Pressing REMOTE places the CCR under external control. In Remote mode, step selection is controlled by remote terminals or network commands. Front-panel step control is disabled. If remote control does not function, verify the CCR is in Remote mode.

FAULT Button

Pressing FAULT displays active fault conditions. Faults may disable output, prevent startup, or indicate protective shutdown. Use the fault screen to identify the cause before restarting.

WARNING Button

Pressing WARNING displays active warning conditions. Warnings indicate abnormal conditions and do not always disable output. Warnings should be investigated but may not require immediate shutdown.

CONFIG Button

Pressing CONFIG accesses the configuration menu. Access requires password entry. The configuration menu allows remote voltage selection, step configuration changes, and advanced parameter settings. Unauthorized configuration changes may affect operation.

Button Operation Notes

Use the arrow buttons to navigate menus and the two dot buttons to perform a corresponding action that will be displayed on screen over the button.



Airport Lighting Company | Type L-828, Type L-829 Ferroresonant Constant Current Regulator

Constant Current Regulator

Related Articles

  • L-828, Type L-829 Ferroresonant Constant Current Regulator (CCR) - Maintenance
    Number of Views54
  • L-828, Type L-829 Ferroresonant Constant Current Regulator (CCR) - Product Overview
    Number of Views118
  • L-828, Type L-829 Ferroresonant Constant Current Regulator (CCR) - Fuse Overview (F1 through F5 Functions)
    Number of Views128
  • L-828, Type L-829 Ferroresonant Constant Current Regulator (CCR) - How to Navigate the CCR Display and Keypad
    Number of Views72
  • L-828, Type L-829 Ferroresonant Constant Current Regulator (CCR) - Understanding the CCR Display Screen
    Number of Views67

Trending Articles

  • L-828, Type L-829 Ferroresonant Constant Current Regulator (CCR) - Adjusting IRMS Warning and Alarm Thresholds
  • Performing Megger Testing for Airfield Lighting Systems
  • L-828, Type L-829 Ferroresonant Constant Current Regulator (CCR) - Completing In-Field Recalibrations
  • L-828, Type L-829 Ferroresonant Constant Current Regulator (CCR) - 24V Internally Powered Remote Wiring
  • L-828, Type L-829 Ferroresonant Constant Current Regulator (CCR) - Understanding the S-1 Cutout
Powered by Salesforce Logo
Loading
L-828, Type L-829 Ferroresonant Constant Current Regulator (CCR) - CCR Keypad Button Functions