Title
CCR Warning – High Input Voltage
URL Name
CCR-Warning-High-Input-Voltage
Summary
Describes the High Input Voltage warning in the Type L-828 and Type L-829 Ferroresonant Constant Current Regulator and the corrective actions.

Content

Warning Description


The voltage input that feeds the CCR is higher than expected. This alarm defaults at 10% over nominal input voltage. When the CCR determines a warning or setpoint alarm, it will engage the indicator light and the warning will be shown on line 1 of the CCR display. The CCR will continue to operate in the event of a warning. Although the CCR will continue operating, warning conditions must still be noted and fixed. Allowing the CCR to operate in a warning state may cause problems for efficiency, general safety, and longevity of equipment.

Attempt to Correct


Always maintain safe working conditions by using appropriate personal protective equipment (PPE) where necessary.
Check the input voltage calibration: refer to How to Determine if Recalibration is Needed.
If the calibration is correct, consult an electrician to diagnose building power problems.

Airport Lighting Company | Type L-828, Type L-829 Ferroresonant Constant Current Regulator

Constant Current Regulator

Related Articles

  • CCR Warning – Low Input Voltage
    Number of Views34
  • CCR Warning – No Input Voltage
    Number of Views32
  • CCR Warning – High Temperature
    Number of Views48
  • CCR Fault – No Input Voltage
    Number of Views54
  • CCR Warning – Off Current High
    Number of Views31

Trending Articles

  • L861 LED Medium Intensity Elevated Edge Light - Replacement Parts
  • Performing Megger Testing for Airfield Lighting Systems
  • L-828, Type L-829 Ferroresonant Constant Current Regulator (CCR) - Completing In-Field Recalibrations
  • L-862(L), L-862E(L) High Intensity LED Runway Light - Installation Instructions
  • L-828, Type L-829 Ferroresonant Constant Current Regulator (CCR) - Fuse Overview (F1 through F5 Functions)
Powered by Salesforce Logo
Loading
CCR Warning – High Input Voltage