CCR Fault – No Input Voltage
URL Name
CCR-Fault-No-Input-Voltage
Summary
Explains the No Input Voltage fault on the Type L-828 / L-829 CCR, when it appears, likely causes, and the manual-listed attempt to correct actions.

Content

Fault Description

The CCR has lost input voltage. This warning will be displayed only if a 24VDC backup power supply is powering the DCMU. The most likely causes of this fault: The CCR feed breaker tripped; Partial or full loss of site power.

Attempt to Correct

Determine if the CCR feed breaker tripped.
If it has, safely turn the breaker back on, put the CCR into Local mode, and turn off the output.
View the warning history in the Diagnostics Menu, refer to Accessing the Diagnostics Menu for more information.
The warning history may provide insight to the cause of tripping the feed breaker.

 

 

Airport Lighting Company | Type L-828, Type L-829 Ferroresonant Constant Current Regulator

Constant Current Regulator

Related Articles

  • CCR Warning – No Input Voltage
    Number of Views33
  • CCR Warning – Low Input Voltage
    Number of Views37
  • CCR Fault – Over Voltage
    Number of Views51
  • CCR Warning – High Input Voltage
    Number of Views40
  • CCR Fault – No Current
    Number of Views62

Trending Articles

  • Performing Megger Testing for Airfield Lighting Systems
  • L-880(L)/L-881(L) Precision Approach Path Indicator (PAPI) - Overview and Application
  • L-828, Type L-829 Ferroresonant Constant Current Regulator (CCR) - Understanding the S-1 Cutout
  • L-828, Type L-829 Ferroresonant Constant Current Regulator (CCR) - 24V Externally Powered Remote Wiring
  • L-849-V-A/E / L-849-I-A/E Unidirectional Runway Approach Lights - Set Up Procedure for a 3 Step CCR
Powered by Salesforce Logo
Loading
CCR Fault – No Input Voltage