CCR Warning – Low Input Voltage
URL Name
CCR-Warning-Low-Input-Voltage
Summary
Describes the Low Input Voltage warning in the Type L-828 and Type L-829 Ferroresonant Constant Current Regulator and the corrective actions.

Content

Warning Description


The voltage input that feeds the CCR is lower than expected. This alarm defaults at 5% under nominal input voltage. When the CCR determines a warning or setpoint alarm, it will engage the indicator light and the warning will be shown on line 1 of the CCR display. The CCR will continue to operate in the event of a warning. Although the CCR will continue operating, warning conditions must still be noted and fixed. Allowing the CCR to operate in a warning state may cause problems for efficiency, general safety, and longevity of equipment.

Attempt to Correct


Always maintain safe working conditions by using appropriate personal protective equipment (PPE) where necessary.
Check the input voltage calibration: refer to How to Determine if Recalibration is Needed.
If the calibration is correct, consult an electrician to diagnose building power problems.

Airport Lighting Company | Type L-828, Type L-829 Ferroresonant Constant Current Regulator

Constant Current Regulator

Related Articles

  • CCR Warning – High Input Voltage
    Number of Views41
  • CCR Warning – No Input Voltage
    Number of Views33
  • CCR Fault – No Input Voltage
    Number of Views56
  • CCR Warning – VA Low
    Number of Views31
  • CCR Warning – Input Card Error
    Number of Views39

Trending Articles

  • Performing Megger Testing for Airfield Lighting Systems
  • Testing a Bridge Rectifier
  • L-849-V-A/E / L-849-I-A/E Unidirectional Runway Approach Lights - Set Up Procedure for a 3 Step CCR
  • L-828, Type L-829 Ferroresonant Constant Current Regulator (CCR) - 24V Externally Powered Remote Wiring
  • L-849(L) REIL Runway End Identification Light/L-859(L) ODAL OMNI Directional Approach Light - System Operation
Powered by Salesforce Logo
Loading
CCR Warning – Low Input Voltage