Title
CCR Warning – Input Card Error
URL Name
CCR-Warning-Input-Card-Error
Summary
Describes the Input Card Error warning in the Type L-828 and Type L-829 Ferroresonant Constant Current Regulator and the corrective actions.

Content

Warning Description


The CCR has determined an error with the input card on the DCMU. When the CCR determines a warning or setpoint alarm, it will engage the indicator light and the warning will be shown on line 1 of the CCR display. The CCR will continue to operate in the event of a warning. Although the CCR will continue operating, warning conditions must still be noted and fixed. Allowing the CCR to operate in a warning state may cause problems for efficiency, general safety, and longevity of equipment.

Attempt to Correct


Always maintain safe working conditions by using appropriate personal protective equipment (PPE) where necessary.
Turn off power to the CCR.
Once power has discharged and all LEDs are out, remove the green terminal blocks from the bottom of the DCMU.
Ensure all screws are tight.
Reinstall the terminal blocks.
Ensure they are seated fully.

Airport Lighting Company | Type L-828, Type L-829 Ferroresonant Constant Current Regulator

Constant Current Regulator

Related Articles

  • CCR Warning – CSS Input Card Failure
    Number of Views36
  • CCR Warning – Firing Card Warning
    Number of Views38
  • CCR Warning – Output Card Fault
    Number of Views50
  • CCR Warning – CSS 123456 Error
    Number of Views33
  • CCR Warning – Low Input Voltage
    Number of Views37

Trending Articles

  • Performing Megger Testing for Airfield Lighting Systems
  • L-828, Type L-829 Ferroresonant Constant Current Regulator (CCR) - 24V Externally Powered Remote Wiring
  • Troubleshooting an L-880(L), L-881(L) Precision Approach Path Indicator Lights (PAPI)
  • L-828, Type L-829 Ferroresonant Constant Current Regulator (CCR) - Understanding the S-1 Cutout
  • L-849-V-A/E / L-849-I-A/E Unidirectional Runway Approach Lights - Set Up Procedure for a 3 Step CCR
Powered by Salesforce Logo
Loading
CCR Warning – Input Card Error