Title
CCR Warning – VA Low
URL Name
CCR-Warning-VA-Low
Summary
Describes the VA Low warning in the Type L-828 and Type L-829 Ferroresonant Constant Current Regulator, including trigger conditions, default threshold, and corrective actions.

Content

Warning Description


The low threshold for VA Changes has been met.
See VA Changes for more information.
This warning defaults to 10%.

Attempt to Correct


Always maintain safe working conditions by using appropriate personal protective equipment (PPE) where necessary.
Verify VA Changes calibration.
Refer to VA Changes.
Put the CCR into Local mode and cycle each step through to determine if the issue persists at each brightness.
While at highest brightness step, do a visual inspection of field equipment to determine if the fixtures have been damaged.

Airport Lighting Company | Type L-828, Type L-829 Ferroresonant Constant Current Regulator

Constant Current Regulator

Related Articles

  • CCR Warning – VA High
    Number of Views33
  • CCR Warning – Low Input Voltage
    Number of Views37
  • CCR Warning – Mismatch - Failsafe
    Number of Views44
  • CCR Warning – Tolerance Warning
    Number of Views35
  • CCR Warning – Output Disabled
    Number of Views41

Trending Articles

  • Performing Megger Testing for Airfield Lighting Systems
  • L-849-V-A/E / L-849-I-A/E Unidirectional Runway Approach Lights - Set Up Procedure for a 3 Step CCR
  • L-828, Type L-829 Ferroresonant Constant Current Regulator (CCR) - 24V Externally Powered Remote Wiring
  • Troubleshooting an L-880(L), L-881(L) Precision Approach Path Indicator Lights (PAPI)
  • L-828, Type L-829 Ferroresonant Constant Current Regulator (CCR) - Understanding the S-1 Cutout
Powered by Salesforce Logo
Loading
CCR Warning – VA Low