Loading
×Sorry to interrupt
CSS Error
Refresh
Skip to Main Content
  • ""
Home Self Help Contact Us

Title
CCR Warning – Output Disabled
URL Name
CCR-Warning-Output-Disabled
Summary
Describes the Output Disabled warning in the Type L-828 and Type L-829 Ferroresonant Constant Current Regulator and the corrective actions.

Content

Warning Description


The "CC as Enable" function is enabled and there is no power being provided to the CC terminal. When the CCR determines a warning or setpoint alarm, it will engage the indicator light and the warning will be shown on line 1 of the CCR display. The CCR will continue to operate in the event of a warning. Although the CCR will continue operating, warning conditions must still be noted and fixed. Allowing the CCR to operate in a warning state may cause problems for efficiency, general safety, and longevity of equipment.

Attempt to Correct


Always maintain safe working conditions by using appropriate personal protective equipment (PPE) where necessary.
Verify if power to the CC terminal was intentionally removed. Resolve conditions that caused the power to be removed. For example, if the CCR is interlocked with a CSS door switch, close the CSS door.
If CC as Enable was unintentionally enabled, navigate to: Configuration Menu > CCR Config > Parallel Inputs > CC as Enable > [Disable].

Airport Lighting Company | Type L-828, Type L-829 Ferroresonant Constant Current Regulator

Constant Current Regulator

Related Articles

  • CCR Warning – Output Card Fault
    Number of Views50
  • CCR Warning – Output Shorted
    Number of Views37
  • L-828, Type L-829 Ferroresonant Constant Current Regulator (CCR) - Operating Modes and Output Current Settings
    Number of Views98
  • CCR Warning – High Temperature
    Number of Views52
  • CCR Warning – Hardware Warning
    Number of Views33

Trending Articles

  • Digital Control and Monitoring Unit (DCMU) – Overview and Function
  • Input Contactor – Operation and Function in the CCR
  • Performing Megger Testing for Airfield Lighting Systems
  • L-828, Type L-829 Ferroresonant Constant Current Regulator (CCR) - Remote Control Overview
  • L-828, Type L-829 Ferroresonant Constant Current Regulator (CCR) - Configuring Automatic Megger (IRMS)
Powered by Salesforce Logo
Loading
CCR Warning – Output Disabled