Title
CCR Fault – No Current
URL Name
CCR-Fault-No-Current
Summary
Describes the No Current fault condition in the Type L-828 and Type L-829 Ferroresonant Constant Current Regulator, including trigger conditions and corrective steps.

Content

Fault Description

The CCR has tried to generate an output current but failed to do so. This fault occurs if the DCMU engages the output and the current stays below 1 amp for approximately 3 seconds. Under normal operation, this fault is a symptom of a problem with the CCR.

Attempt to Correct

  • Follow lock out / tag out procedures and verify all sources of electricity are open before working on the CCR.
  • With the CCR powered off, check each installed fuse.
  • Once power has discharged and all LEDs are out:
  • Remove the green terminal blocks from the firing card and DCMU.
  • Ensure all screws are tight.
  • Reinstall the terminal blocks and ensure they are seated fully.
  • Unscrew the serial cable at both ends and remove it.
  • Reinstall the cable and secure it using the thumbscrews.

 

Airport Lighting Company | Type L-828, Type L-829 Ferroresonant Constant Current Regulator

Constant Current Regulator

Related Articles

  • CCR Fault – Over Current
    Number of Views51
  • CCR Fault – Over Voltage
    Number of Views52
  • CCR Fault – No Input Voltage
    Number of Views56
  • CCR Fault – Unknown Fault
    Number of Views42
  • CCR Fault – Current Asymmetry
    Number of Views73

Trending Articles

  • Performing Megger Testing for Airfield Lighting Systems
  • Digital Control and Monitoring Unit (DCMU) – Overview and Function
  • Troubleshooting an L-880(L), L-881(L) Precision Approach Path Indicator Lights (PAPI)
  • L-880(L), L-881(L) Precision Approach Path Indicator Lights (PAPI) - Leveling and Tilting the Light Head (Setting the glid…
  • Testing a Bridge Rectifier
Powered by Salesforce Logo
Loading
CCR Fault – No Current