CCR Warning – Output Shorted
URL Name
CCR-Warning-Output-Shorted
Summary
Describes the Output Shorted warning in the Type L-828 and Type L-829 Ferroresonant Constant Current Regulator, including cause, operation in shorted condition, and corrective actions.

Content

Warning Description


The CCR is providing output current, but the voltage is minimal.
TURN The CCR providing output current, but the voltage is minimal.
The most likely cause is an S-1 Cutout shorting the output, or a forgotten wire jumper used during setup/calibration.
The CCR will operate in a short, and is providing power to the output terminals.

Attempt to Correct


Always maintain safe working conditions by using appropriate personal protective equipment (PPE) where necessary.
Go into Monitor Config > Output Voltage and disable it, if the warning disappears re enable if desired and configure the appropriate threshold determined by load.
TURN OFF POWER to the CCR before modifying the output circuit.
Ensure the circuit S-1 Cutout is set for normal operation.
Open the CCR door and visually inspect for a short, such as a leftover wire jumper from installation.
If there is still a short, disconnect airfield circuit and test for a circuit short.

Airport Lighting Company | Type L-828, Type L-829 Ferroresonant Constant Current Regulator

Constant Current Regulator

Related Articles

  • CCR Warning – Output Disabled
    Number of Views45
  • CCR Warning – Output Card Fault
    Number of Views57
  • L-828, Type L-829 Ferroresonant Constant Current Regulator (CCR) - Operating Modes and Output Current Settings
    Number of Views107
  • CCR Warning – Tolerance Alarm
    Number of Views39
  • CCR Warning – Mismatch - Failsafe
    Number of Views48

Trending Articles

  • Performing Megger Testing for Airfield Lighting Systems
  • L-849(L) REIL Runway End Identification Light/L-859(L) ODAL OMNI Directional Approach Light - Replacement Parts
  • Current Transformers (CTs) – Function in the CCR
  • CCR Fault – Over Voltage
  • Troubleshooting an L849(L) SAL-1030 Runway End Identifier Light (REIL) System
Powered by Salesforce Logo
Loading
CCR Warning – Output Shorted