Warning Description


The "CC as Enable" function is enabled and there is no power being provided to the CC terminal. When the CCR determines a warning or setpoint alarm, it will engage the indicator light and the warning will be shown on line 1 of the CCR display. The CCR will continue to operate in the event of a warning. Although the CCR will continue operating, warning conditions must still be noted and fixed. Allowing the CCR to operate in a warning state may cause problems for efficiency, general safety, and longevity of equipment.

Attempt to Correct


Always maintain safe working conditions by using appropriate personal protective equipment (PPE) where necessary.
Verify if power to the CC terminal was intentionally removed. Resolve conditions that caused the power to be removed. For example, if the CCR is interlocked with a CSS door switch, close the CSS door.
If CC as Enable was unintentionally enabled, navigate to: Configuration Menu > CCR Config > Parallel Inputs > CC as Enable > [Disable].

Airport Lighting Company | Type L-828, Type L-829 Ferroresonant Constant Current Regulator

Constant Current Regulator

Related Articles

  • CCR Warning – Output Card Fault
    Number of Views43
  • CCR Warning – Output Shorted
    Number of Views34
  • Verifying Isolation Transformer Output Current / Fixture Input Current
    Number of Views148
  • CCR Warning – Mismatch - Failsafe
    Number of Views37
  • CCR Warning – Tolerance Warning
    Number of Views32

Trending Articles

  • L-862(L), L-862E(L) High Intensity LED Runway Light - Replacement Parts
  • L-880(L), L-881(L) Precision Approach Path Indicator Lights (PAPI) - Installation Instructions
  • L-880(L), L-881(L) Precision Approach Path Indicator Lights (PAPI) - Performance Information
  • L-828, Type L-829 Ferroresonant Constant Current Regulator (CCR) - Adjusting IRMS Warning and Alarm Thresholds
  • CCR Fault Codes – Overview
Powered by Salesforce Logo
Loading
CCR Warning – Output Disabled