Input Contactor – Operation and Function in the CCR
URL Name
Input-Contactor-Operation-and-Function-in-the-CCR
Summary
Explains the purpose and operation of the input contactor in the Type L-828 and L-829 Constant Current Regulators.

Content

Overview


The input contactor controls the application of input power to the CCR. It is an electrically controlled switching device that connects or disconnects facility power from the regulator’s internal circuitry.

Primary Function


The input contactor connects incoming line voltage to the regulator when the CCR is turned ON. It disconnects input power when the CCR is turned OFF. It is controlled by the CCR control system. It provides controlled energization of the transformer and associated components.

Operation During Start-Up


When the CCR is commanded to turn ON, the control system energizes the contactor coil. The contactor closes. Input power is applied to the regulator. When the CCR is turned OFF, the coil is de-energized. The contactor opens. Input power is removed from the main power circuit.

Relationship to Control System


The input contactor operates under control of the DCMU and associated circuitry. It does not operate independently. It responds to local ON/OFF commands, remote control inputs, and fault conditions. If certain fault conditions occur, the control system may de-energize the contactor.

Safety Considerations


Even when the contactor is open, upstream input terminals may still be energized. Lockout/tagout is required before servicing. The input contactor does not replace upstream disconnect devices.

Mechanical Wear


Unlike the SSR, the input contactor is a mechanical device. It may experience contact wear over time, coil failure, and mechanical fatigue. Periodic inspection and maintenance may be required.

Airport Lighting Company | Type L-828, Type L-829 Ferroresonant Constant Current Regulator

Constant Current Regulator

Related Articles

  • Firing Card – Control Interface and Function in the CCR
    Number of Views51
  • Input Surge Arrestor – Function in the CCR
    Number of Views50
  • Current Transformers (CTs) – Function in the CCR
    Number of Views41
  • Output Surge Arrestors – Function in the CCR
    Number of Views44
  • Solid State Relay (SSR) – Function in the CCR
    Number of Views44

Trending Articles

  • Performing Megger Testing for Airfield Lighting Systems
  • Testing a Bridge Rectifier
  • L-849-V-A/E / L-849-I-A/E Unidirectional Runway Approach Lights - Set Up Procedure for a 3 Step CCR
  • L-828, Type L-829 Ferroresonant Constant Current Regulator (CCR) - 24V Externally Powered Remote Wiring
  • L-849(L) REIL Runway End Identification Light/L-859(L) ODAL OMNI Directional Approach Light - System Operation
Powered by Salesforce Logo
Loading
Input Contactor – Operation and Function in the CCR