Describes the VA High warning in the Type L-828 and Type L-829 Ferroresonant Constant Current Regulator, including trigger conditions, default threshold, and corrective actions.

Content

Warning Description


The high threshold for VA Changes has been met.
See VA Changes for more information.
This warning defaults to 10%.

Attempt to Correct


Always maintain safe working conditions by using appropriate personal protective equipment (PPE) where necessary.
Verify VA Changes calibration.
Refer to CCR Changes.
Put the CCR into Local mode and cycle each step through to determine if the issue persists at each brightness.
While at highest brightness step, do a visual inspection of field equipment to determine if the fixtures have been damaged.

Airport Lighting Company | Type L-828, Type L-829 Ferroresonant Constant Current Regulator

Constant Current Regulator

Related Articles

  • CCR Warning – VA Low
    Number of Views27
  • CCR Warning – High Temperature
    Number of Views44
  • CCR Warning – High Input Voltage
    Number of Views35
  • CCR Warning – Off Current High
    Number of Views30
  • CCR Warning – Mismatch - Failsafe
    Number of Views36

Trending Articles

  • L-828, Type L-829 Ferroresonant Constant Current Regulator (CCR) - Adjusting IRMS Warning and Alarm Thresholds
  • CCR Fault Codes – Overview
  • Performing Megger Testing for Airfield Lighting Systems
  • L-828, Type L-829 Ferroresonant Constant Current Regulator (CCR) - Understanding the S-1 Cutout
  • L-828, Type L-829 Ferroresonant Constant Current Regulator (CCR) - 24V Internally Powered Remote Wiring
Powered by Salesforce Logo
Loading
CCR Warning – VA High